
- (01-10) -
SPECIFICATIONS
Model
No.
Power
Source Notch
Heat Exchange Ventilation Normal Ventilation
Product
Weight
Input Current Air
Volume
External
Static
Pressure
Temperature
Exchange
Exchange
Noise Input Current Air
Volume
External
Static
Pressure
Noise
(Hz) (W) (A) (m3/h) (Pa) Cooling Heating (dB) (W) (A) (m3/h) (Pa) (dB) (kg)
UTZ-
BD080B
220-240V
a.c.
Extra High
50 387-418 1.74-1.76 800 140 75 65 71 37.0-37.5 387-418 1.74-1.76 800 140 37.0-37.5
71
High
50 360-378 1.58-1.64 800 110 75 65 71 36.5-37.0 360-378 1.58-1.64 800 110 36.5-37.0
Low
50 293-295 1.23-1.33 630
55 76 68 74 33.5-34.5 293-295 1.23-1.33 630
55 33.5-34.5
PERFORMANCE
400
0 100 200 300 400 500 600 700 800 900 1000 1100 1200
50
100
150
200
300
0 100 200 300 400 500 600 700
Air Volume (m3/h)
Air Volume (ft3/min)
External Static Pressure (Pa)
80
50
60
70
Duct resistance Curve
P-Q Curve 220 - 240V ~ 50Hz
T
e
m
p
e
r
a
t
u
r
e
E
n
t
h
a
l
p
(
i
n
h
e
a
t
i
n
g
)
E
nt
h
a
l
p
(
i
n
c
o
o
l
i
n
g
)
Extra High
Equivalent pipe length
High
Low
of pipe (duct) : =0.02
100m
60
40
250
20
350
80
90450
500
Use conditions
Outdoor air conditions
Indoor air conditions
Installation requirements
Same as the indoor air conditions
*
Indoor air here means air in air-conditioned
living rooms.
Its use in refrigerators or other places
Example Indoor air conditions
During cooling period
During heating period
mentioned air volume.
averages that of when cooling and when
heating.
MOTOR
SPECIFICATIONS
induction motor
Rating Cont.
Insulation Class class E
Temperature Rise under 75 K
Sorrounding Temperature
-1040
Insulation Resistance
Withstand Voltage