- (01-08) -
SPECIFICATIONS
Model
No.
Power
Source Notch
Heat Exchange Ventilation Normal Ventilation
Product
Weight
Input Current Air
Volume
External
Static
Pressure
Temperature
Exchange
Exchange
Noise Input Current Air
Volume
External
Static
Pressure
Noise
(Hz) (W) (A) (m3/h) (Pa) Cooling Heating (dB) (W) (A) (m3/h) (Pa) (dB) (kg)
UTZ-
BD050B
220-240V
a.c.
Extra High
50 263-289 1.20-1.21 500 120 75 62 67 36.5-37.5 263-289 1.20-1.21 500 120 36.5-37.5
57
High
50 204-225 0.93-0.94 500 60 75 62 67 34.5-35.5 204-225 0.93-0.94 500 60 34.5-35.5
Low
50 165-185 0.75-0.77 440
35
76 64 69 31.0-32.5 165-185 0.75-0.77 440
35
31.0-32.5
PERFORMANCE
Use conditions
Outdoor air conditions
Indoor air conditions
Installation requirements
Same as the indoor air conditions
*
Indoor air here means air in air-conditioned
living rooms.
Its use in refrigerators or other places
Example Indoor air conditions
During cooling period
During heating period
mentioned air volume.
averages that of when cooling and when
heating.
MOTOR
SPECIFICATIONS
induction motor
Rating Cont.
Insulation Class class E
Temperature Rise under 75 K
Sorrounding Temperature
-1040
Insulation Resistance
Withstand Voltage
400
0 100 200 300 400 500 600 700 800
50
100
150
200
300
0 50 100 150 200 250 300 350 400 450
Air Volume (m3/h)
Air Volume (ft3/min)
External Static Pressure (Pa)
80
50
60
70
Duct resistance Curve
P-Q Curve 220 - 240V ~ 50Hz
T
e
m
p
e
r
a
t
u
r
e
E
n
t
h
a
l
p
(
i
n
h
e
a
t
i
n
g
)
E
n
t
h
a
l
p
(
i
n
c
o
o
l
i
n
g
)
Extra High
Equivalent pipe length
High
Low
: =0.02
100m
60
40
250
20
350
80