- (02 - 07) -
OUTDOOR UNIT
AOÝG09-12LLC
OUTDOOR UNIT
AOÝG09-12LLC
MODEL
¢ : AOÝG12LLC
Height difference H
Ý1 Indoor unit is higher than outdoor unit. Ý2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
57.5 10 15
Height difference H
(m)
Û1
Indoor unit is higher
than outdoor unit.
10 - - 0.908 0.875
7.5 - 0.954 0.908 0.875
5 1.000 0.954 0.908 0.875
0 1.000 0.954 0.908 0.875
Û2
Indoor unit is lower
than outdoor unit
-5 0.995 0.949 0.903 0.870
-7.5 -0.947 0.902 0.868
-10 - - 0.900 0.867
COOLING
Pipe length (m)
57.5 10 15
Height difference H
(m)
Û1
Indoor unit is higher
than outdoor unit.
10 - - 0.957 0.911
7.5 -0.974 0.961 0.916
5 0.992 0.978 0.965 0.919
0 1.000 0.986 0.972 0.927
Û2
Indoor unit is lower
than outdoor unit
-5 1.000 0.986 0.972 0.927
-7.5 - 0.986 0.972 0.927
-10 - - 0.972 0.927