7
4 Install lock
4a Install magnet and secure with screws.
5 Connect wiring to board (basic model).
5a Connect plug and wires to board.
COILS
+ - FIRE AUX
PWR
RLS
Power Input
12/24V DC
UL 294 Listed, power
limited, Class 2, power
supply must be used
RST
Fire Alarm Input
Apply a
normally closed
dry contact or a
jumper if not
connected to fire
alarm.
Release Input
Dry contact
closure will
release lock for
the time delay
period.
Reset Input
Dry contact
closure resets
lock in alarm
condition.
Auxiliary Input
Apply a normally
closed dry contact or
a jumper if not using.
Opening dry contact
places lock into delayed
egress countdown.
COILS
+ - FIRE AUX
PWR
RLSRST NOC
ALRM
Alarm Output (Optional)
Contacts change state
during an alarm condition.
30V@1A resistive
see “Wire Gauge and Length
.
5b Set SW2 dip switches.
LNOTE: Dip switch panel may be upside-down, depending on installation. Look for the “OFF” label and
compare to the images below for correct dip switch positions.
Feature Switch Setting Description
Nuisance Delay 0 seconds 1 second 2 seconds 3 seconds Nuisance delay is the amount of time the door must be pushed
or aux input must be pressed before triggering the Delayed
Egress Cycle. Programmable to 0-3 seconds.
1Off On Off On
2Off Off On On
Nuisance Alert 3 Off=Disabled On=Enabled Causes horn to sound during nuisance delay
Auto Relock 4 Off=Disabled On=Enabled When enabled, lock will energize upon regaining power or
Anti-Tailgate
(Plus Model Only)
5 Off=Disabled On=Enabled Door will relock as soon as it closes – even if the relock time
delay has not ended.
Door Propped/Forced
(Plus Model Only)
6 Off=Disabled On=Enabled Enables door propped and door forced alarms
Unlock Alert 7 Off=Disabled On=Enabled Horn sounds whenever door is unlocked and power is still
applied to the door
DEL Enabled 8 Off=Disabled On=Enabled Enables or disables the DEL plunger switch. Aux Input will
always function even if DEL plunger switch is disabled.
Actual Size
Rocker Down
O
F
F
OFF
ON