Loading...
page 13
AK and 3K Series Installation and Service Instructions
4211-143-A 02-19-10
The AK Generator design may incorporate several modification options. Options such as automatic tank draining and others are available. Please call the AMEREC
Service Department at 1-800-331-0349 for instructions and availability of these options.
There are no user serviceable parts in the Generator. All repair should be performed by a qualified service person. For additional assistance or the factory authorized
service person nearest you call the AMEREC Service Department at 1-800-331-0349. The Trouble Shooting Guide below is meant as a general aid only. Follow ACTION
TO BE TAKEN in order until the problem is resolved. Where replacements or repairs are indicated, see the appropriate paragraph of SECTION: 8 SERVICE.
SECTION 9: OPTIONAL MODIFICATIONS
SECTION: 10 TROUBLE SHOOTING GUIDE
SYMPTOMS PROBABLE CAUSES ACTION TO BE TAKEN
Control won't turn "ON"
(Control light off).
Note: Control Cables must
be correctly plugged in
before power is turned on.
Improper power supplied (no power).
or
Control improperly connected.
or
"PCA" printed circuit assembly is faulty.
or
Control cable is faulty.
or
Conto l is faulty.
1. a. Make sure circuit breaker is "ON", 208/240V supplied.
b. Using a voltmeter, check the voltage across the two fuses on the "PCA"
printed circuit assembly. Voltage should be 208V to 240V.
c. Check fuses on the PCA. If fuse(s) are blown, replace with Buss#
MDL 10/100 or equivalent fuse. If the fuse blows again - call AMEREC's
Service Department.
2. Turn off power to the generator.
3. Check control(s) installed per Section 6-5. Re-apply power and test operation.
4. Replace PCA printed circuit assembly - call AMEREC's Service Department.
5. Replace control cable - call AMEREC's Service Department.
6. Replace the control - Call AMEREC's Service Department.
Control "OFF". (Control light
off)
Water won't shut off and runs
out of the steam head.
Water solenoid valve is stuck open.
or
"PCA" printed circuit assembly is faulty.
1. Turn off power to the generator. If the water stops, go to step 3.
2. a. Remove the water solenoid valve, dissassemble, clean,
re-assemble, and check for proper operation.
b. Replace valve - call AMEREC's Service Department.
3. Replace the "PCA" printed circuit assembly - call AMEREC's Service Department.
Control "ON". (Control light
on)
Water won't shut off and runs
out of the steam head.
"PCA" printed circuit assembly is faulty.
or
Connection between the blue wire and the
water level probe is faulty.
1. Check that the blue & white wires are properly attached to the water level probe.
Blue wire to the shortest level probe,white to the highest probes.
2.Replace the "PCA" printed circuit assembly - call AMEREC's Service Department.
Control "ON" (Control light
on), Tank drained.
Unit won't fill.
No water supplied (turned off?)
or
Plugged water solenoid valve.
or
Water solenoid valve is faulty.
or
"PCA" printed circuit assembly is faulty.
or
Level probe is faulty.
1. Check for proper water supply (Supply valve "on"). Check for closed drain valve.
2. Remove the blue wire from the level probe. If the unit fills, clean or replace the
level probe.
3. Reconnect the blue wire to the shortest level probe. At the water valve solenoid,
slide back the blue connector enough to get the voltmeter probes on the
solenoid terminals. Measure the voltage across the solenoid terminals. If it is
not 208V / 240V, replace the printed circuit assembly. If 208V / 240V is found
proceed with steps 4 & 5.
4. Remove water solenoid valve; disassemble, clean, reassemble, and check for
proper operation.
5. Replace the water solenoid valve - call AMEREC's Service Department.
Loading...
Terms of Use | Privacy Policy | DMCA Policy
2006-2020 Rsmanuals.com