AK and 3K Series Installation and Service Instructions
4211-139-A 08-14-2009
ELECTRICAL INFORMATION CHART
DIAGRAM 11 DIAGRAM 12
(BUILT-IN SENSOR ON KT60
CONTROL ONLY)
USED WITH K60 OR K30 CONTROL ONLY
TILE UP TO 50 mm
DIAMETER HOLE
IN FINISHED WALL
WALL
DECORATIVE
CONTROL COVER
PLATE
CONTROL
HOUSING
DIAGRAM 13
APPLY SEALANT
(100% SILICONE CAULK)
TILE UP TO
45 mm DIAMETER
HOLE IN FINISHED
WALL
(OPTIONAL NUT IF BACK OF
WALL IS ACCESSABLE)
2 GANG ROUGH-IN BOX
DIAGRAM 14
R30K
ROUGH-IN K30, K60, KT60
ROUGH-IN
SILICONE
CAULK
TEMPERATURE
SENSOR
WALL
22 mm
HOLE
SENSOR
CABLE
PIGTAIL
PROBE MUST
BE POINTED
DOWN
STEAM
GENERATOR
MODEL kW
AC
VOLTAGE PHASE
NOMINAL
WATTS
NOMINAL
AMPS
RECOMMENDED
SAFETY DEVICE
4kW 230V~ N 1 4133 18,0 25
5kW 230V~ N 1 5051 22,0 30
6kW 230V~ N 1 5970 26,0 35
7kW 230V~ N 1 6888 29,9 40
8kW 230V~ N 1 7806 33,9 45
10kW 230V~ N 1 9184 39,9 50
12kW 230V~ N 1 11939 51,9 65
8kW 400V~ N
3 3 7806 11,3 15
10kW 400V~ N
3 3 10102 14,6 20
12kW 400V~ N
3 3 11939 17,2 25
14kW 400V~ N
3 3 13776 19,9 25
Notes: Use only copper wire rated 600V~ and 75°C or better
All models require Earth connection
All models require Mains plus Neutral connections
All Mains must supply minimum 195V ~ to N while steamer is heating
Steamer must be connected to a means of disconnecting all mains supply
connections after installation