Alarm Actions
12.2.6. Email / Text Message
If the "Email/Text Message" action is selected, NetLink II can send an
email or text message to a user-defined address when an alarm is generated.
Notes:
In order to use the Email / Text Message action, target
email addresses must first be defined via the Network Port
Configuration Menu, Item 38, as described in Section 5.4.5.
The Address that is entered in the "Mail To:" field will determine
whether an email or text message is sent when this type of action
is performed. If a cell address (e.g., 5551234@cellservice.com)
is entered in the "Mail To" field, a text message will be sent; if an
email message is entered in the "Mail To" field, an email will be
sent.
When the Email action is selected, the following item must be defined at the
configuration menu for the specified alarm.
Email/Message To: Selects one or both of the two email addresses
that are defined via the Network Port Parameters menu.
Message: (Optional) Enter a message to describe the type of alarm
event that occurred; for example "80% FULL".
12.2.7. Console
If this action is selected, NetLink II will send a message via the Console
Port when an alarm is generated. Typically, this message describes the type
of alarm event that occurred. NetLink II can also execute a user-defined
command string to report status or download data.
Note: In order to use the Console action, Console Port
communication parameters must first be defined as described in
Section 5.4.3.
When the Console action is selected, the following items should be defined
at the configuration menu for the specified alarm.
Message: (Optional) Enter a message to describe the type of alarm
event that occurred; for example "80% FULL".
Auto-Execute: (Optional) Enable or disable the Auto-execute
function and then define the command string at the "Execute
Commands" prompt. Auto Execute command strings are discussed
further in Section 12.3.