Reset/NoDialtoneScaler: Determines the number of Periodic Modem Reset
sequences that must occur in order to initiate a No Dialtone Check. If this
parameter is set to "0," then the No Dialtone Alarm will not function. When
both this parameter and the Reset/No Dialtone Interval are set to a value
from 1 to 99 and the No Dialtone Alarm is enabled, the RSM will initiate a No
Dialtone Check after a time period equal to the defined Reset/No Dialtone
IntervalvaluemultipliedbytheReset/NoDialtoneScalervalue.(Default=16)
ModemPPPMode: Allows data that is normally sent via Ethernet to be sent via
phone line. When Modem PPP Mode is selected, the following modem-related
parameters will be available:
Note:WhencommunicatingwiththeRPCviamodem,ModemPPPMode
parameterswillnotbechangeduntilafteryouexitcommandmodeand
disconnect.
ModemResetString: Redefines the modem reset string. The Reset String
canbesentpriortotheInitializationstring.(Default=ATZ.)
ModemInitializationString: Defines a command string that is used to
initialize the modem to settings required for PPP communication
(Default=ATQ0V1E1S0=0&C1&D2)
ModemHang-UpString: Although the RPC will pulse the DTR line to hang-
up an attached modem, the Hang-Up string is often useful for controlling
modemsthatdonotusetheDTRline.(Default=undefined.)
Reset/NoDialtoneInterval: Determines how often the Reset String will
be sent to the modem at this port and also sets the trigger value for the No
Dialtone Alarm. For more information on the No Dialtone Alarm, please refer
toSection8.9.(Default=15Minutes)
NoDialtoneAlarmEnable: When this item is "On" the No Dialtone Alarm
can be enabled as described in Section 8.9. When the No Dialtone Alarm is
enabled, the RPC can provide notification if the unit detects that a phone line
connectedtoamodeminstalledatthisportisdead.(Default=Off.)
Reset/NoDialtoneScaler: Determines the number of Periodic Modem Reset
sequences that must occur in order to initiate a No Dialtone Check. If this
parameter is set to "0," then the No Dialtone Alarm will not function. When
both this parameter and the Reset/No Dialtone Interval are set to a value
from 1 to 99 and the No Dialtone Alarm is enabled, the RSM will initiate a No
Dialtone Check after a time period equal to the defined Reset/No Dialtone
IntervalvaluemultipliedbytheReset/NoDialtoneScalervalue.(Default=16)
PeriodicResetLocation: The IP address or URL for the website that will
be used to keep the PPP connection alive when not in use. The RPC will
regularly ping the selected IP address or URL in order to keep the connection
alive.(Default=undefined)
Notes:
• InordertoselectadomainnameasthePeriodicResetLocation,youmust
firstdefinetheDomainNameServersasdescribedinSection6.8.4.
• TheIPAddress,P-t-PandSubnetMaskparameterscannotbedefined
bytheuserandwillbeautomaticallysuppliedbytheISPwhenaPPP
communication is started..