Loading...
6-10
Configuration Options
6.2.3.1. Audit Log and Alarm Log Configuration Options
The Log Configuration options in the System Parameters menu allows you to enable/
disable and configure the Audit Log and Alarm Log. The Audit Log and Alarm Log both
offer the following parameters:
• Off: The Log is disabled, and command activity and/or alarm events will not be
logged.
• On-WithSyslog: The Log is enabled, and power switching, login/logout activity
and/or alarm events will be logged. The RPC will generate a Syslog Message every
time a Log record is created.
• On-WithoutSyslog: The Log is enabled, and power switching, login/logout
activity and/or alarm events will be logged, but the RPC will not generate a Syslog
Message every time a Log record is created. (Default Setting.)
Notes:
• InorderfortheAuditLogorAlarmLogtogenerateSyslogMessages,Syslog
Parameters must first be defined as described in Section 11.
• TheAuditLogwilltruncateusernamesthatarelongerthan22characters,
anddisplaytwodots(..)inplaceoftheremainingcharacters.
6.2.3.2. Reading, Downloading and Erasing Logs
To read or download the status logs, proceed as follows:
• TextInterface: Type /L and press [Enter] to access the Display Log menu. Select
the desired option, key in the appropriate number, press [Enter] and then follow the
instructions in the "Display Logs" submenu. In the text interface, The Display Logs
menu is used to download or display the Audit Log and Alarm Log.
• WebBrowserInterface: Move the cursor over the "Logs" link. When the flyout
menu appears, click on the desired option and then follow the instructions in the
resulting submenu.
Proceed as follows to download, display or erase logged data:
• AuditLogandAlarmLog: The Audit Log and Alarm Log can be displayed or
downloaded via either the Text Interface or Web Browser Interface. When the Audit
Log or Alarm Log are displayed via the Text Interface, the RPC will also offer the
option to erase Audit Log or Alarm Log data.
• TemperatureLog: The Temperature Log can be displayed or downloaded
via either the Text Interface or Web Browser Interface. When the Temperature
Log is selected via the Text Interface, the RPC will also offer the option to erase
Temperature Log data.