Loading...
6-4
Configuration Options
• ScriptingOptions: Provides access to parameters that are used to set up the RPC
unit for running various scripts as described in Section 6.2.5.
Notes:
• ThefunctionsprovidedbytheScriptingOptionsmenuareintendedforusein
applicationswherescriptsareemployedtocontrolRPCoperation.Improper
useofScriptingOptionsmenufunctionscancausetheRPCunittobecome
unresponsive.Priortoattemptingtousethefunctionsprovidedbythe
ScriptingOptionsmenu,pleasecontactWTITechnicalSupportasdescribed
inAppendixDinthisUser'sGuide.
• IntheTextInterface,theScriptingOptionssubmenuisaccessedviaitem12.
ToaccesstheScriptingOptionsparametersviatheWebBrowserInterface,
placethecursoroverthe"GeneralParameters"link,waitfortheflyoutmenu
toappear,thenclickonthe"ScriptingOptions"link.
• EnergyWiseConfiguration: Defines parameters that are needed in order for the
RPC to serve as an element in a Cisco® EnergyWise™ network. This item allows
thefollowingparameterstobedefined.(Default=Off.)
Note:IntheWebBrowserInterface,EnergyWiseparametersaredefinedvia
the"EnergyWise"linkintheGeneralParametersfly-outmenu.
Enable: Enables/disables the RPC unit's ability to particapate in a Cisco
Energywisenetwork.(Default=Off)
Domain: The Energywise Domain Name; up to eighty characters long.
(Default=undefined.)
Secret: A password that is used to authenticate each element in a Cisco
Energywise network. The Secret parameter can be up to eighty characters long.
(Default=undefined.)
• AssetTag: Allows a descriptive tag or tracking number to be assigned to the RPC
unit. Once defined, the Asset Tag can be displayed via the Product Status Screen
in the Web Interface or via the /J* command in the Text Interface.
(Default=Undefined)
• LoginBanner: Allows definition of a banner/message that will be displayed when a
valid username and password are entered during log in. The Login Banner can be
used to post legal warning regarding unauthorized access to the unit or to display
otheruser-definedinformationorinstructions.(Default=Undefined)
Notes:
• AlthoughtheLoginBannerwillbedisplayedwhentheRPCisaccessedvia
boththeTextInterfaceandWebBrowserInterface,theLoginBannercanonly
bedefinedviatheTextInterface.
• TheLoginBannercanbeupto1024characterslong.
• TheLoginBannertextmustbeginwiththe<banner> command and end
with the </banner> command.
• Bannertextcanbecopiedandpastedfromatexteditor,orsentinfromafile.
• Forbestresults,theindividualtextlinesintheLoginBannershouldbeless
than80characterswide.