17-2
Command Reference Guide
17.2. Command Summary
Function Command Syntax Command Access Level
Admin. SuperUser User ViewOnly
Display
Circuit Status /S [s] [Enter] XXXX
Port Diagnostics /SD[Enter] XXXX
Port Parameters (Who) /W [n][Enter] XXXX
Circuit Group Status /SG [Enter] XXXX
Network Status /SN [Enter] X X X X
Network Configuration Summary /RN[Enter] X X X X
IP Alias Status /SA[Enter] X X XX
Alarm Status /AS[Enter] X
Help Menu /H [Enter] XXXX
Log Functions /L [Enter] X X
Site ID / Unit Information /J [*] [Enter]X X X X
Control
Exit Command Mode /X [Enter] X X X X
Boot Circuit n/BOOT <s>[,Y] [Enter]X X X
Turn Circuit n On /ON <s>[,Y] [Enter]X X X
Turn Circuit n Off /OFF <s>[,Y] [Enter]X X X
Default All Circuits /DPL[,Y] [Enter]X X X
Connect to Port /C [n] [Enter] X X X
Disconnect from Port /D [n][Enter] X X X
Send Parameter File /U [Enter] X
Send SSH Keys /K <k> [Enter] X
Unlock Invalid Access /UL [Enter] X
Outbound Telnet /TELNET <ip> [port] [raw][Enter] XXX
Outbound SSH /SSH <ip> -l <username>[Enter] XX
Configuration
System Parameters /F [Enter] X
Console Port Parameters /P [n] [Enter] X
Circuit Parameters /PL [Enter] X
Circuit Group Parameters /G [Enter] X
Network Configuration - IPv4 /N [Enter] X
Network Configuration - IPv4/IPv6 /N*[Enter] X
Reboot Options /RB [Enter] X
Alarm Configuration /AC [Enter] X
Reboot System /I [Enter] X
Upgrade Firmware /UF [Enter] X
Test Network Configuration /TEST [Enter] X
In Administrator Mode and SuperUser Mode, all RPC circuits are displayed. In User Mode and ViewOnly Mode,
the Circuit Status Screen will only include the circuits that are allowed by your account.
In Administrator Mode, all Circuit Groups are displayed. In SuperUser Mode, User Mode and ViewOnly Mode,
the Circuit Group Status Screen will only include the Circuit Groups that are allowed by your account.
In Administrator Mode, the Help Menus will list all RPC commands. In the SuperUser Mode, User Mode and
ViewOnly Mode, the Help Menus will only list the commands that are allowed by the access level.
If the optional asterisk (*) argument is included in the command line, this command will also show model
numbers, software versions and other information for the RPC unit.
The ",Y" argument can be included in the command line to suppress the command confirmation prompt.
In order to invoke this command, Outbound Telnet/SSH and Outbound SErvice Access must be enabled for
your account.
In SuperUser Mode, configuration menus can be displayed, but parameters cannot be changed.