Loading...
2-5
Unit Description
2.5. Additional Button Functions
The Default and Reset buttons can be used to perform the functions described below:
Notes:
• AllbuttonfunctionscanalsobedisabledviatheSystemParametersmenu,as
described in Section 6.2.
• WhentheRPCisresettofactorydefaults,alluser-definedconfiguration
parameters will be cleared, and the default “super” user account will also be
restored.
1. RebootOperatingSystem:
a) Press and hold the Reset button for five seconds, and then release it.
b) The RPC will reboot its operating system; all circuits will be left in their current
On/Off state.
2. SetParameterstoFactoryDefaults:
a) Simultaneously press both the Default button and the Reset button, hold them
for five seconds, and then release them.
b) All RPC parameters will be reset to their original factory default settings, and
the unit will then reboot. All circuits will be left in their current On/Off state.
3. Toggle/DefaultAllCircuits:
a) Press the Default button, hold it for five seconds, and then release the Default
Button.
b) The RPC will switch all circuits to the Off state. If all circuits are already in the
Off state, then the unit will reset all circuits to their user defined default states.