8-17
Alarm Configuration
8.8. The Emergency Shutoff Alarm
The Emergency Shutoff Alarm can provide notification when the Emergency Shutoff
feature is triggered.
Notes:
• InorderfortheRPCtoprovidealarmnotificationviaEmail,communication
parametersmustfirstbedefinedasdescribedinSection6.8.10.
• InorderfortheRPCtoprovidealarmnotificationviaSyslogMessage,Syslog
parametersmustfirstbedefinedandSyslogMessagesmustbeenabledas
describedinSection6.8andSection11.
• InorderfortheRPCtoprovidealarmnotificationviaSNMPTrap,SNMP
parametersmustfirstbedefined,andSNMPTrapsmustbeenabledas
describedinSection6.8.6andSection12.
To configure the Emergency Shutoff Alarm, you must access command mode using
a password that permits Administrator Level commands. The Lost Voltage Alarm
Configuration menu offers the following parameters:
• TriggerEnable: Enables/Disables the trigger for this alarm. When disabled, this
alarmwillbesuppressed.(Default=On)
Note:
• Tocancelanalarmwithoutcorrectingtheconditionthatcausedthealarm,
simplytoggletheTriggerEnableparameterOffandthenbackOnagain.
• TheTriggerEnable,NotifyUponClear,EmailMessageandAddress1,2
and3Parametersallinclude"CopytoAllTriggers"optionsthatallowyouto
enable/disablethecorrespondingparameterforallalarms.Forexample,if
theLostVoltageAlarm'sTriggerEnableparameterissetto"On(CopytoAll
Triggers),thenallotheralarmswillalsobeenabled.
• ResendDelay: Determines how long the RPC will wait to resend an email
message generated by this alarm, when the initial attempt to send the notification
wasunsuccessful.(Default=60Minutes)
• NotifyUponClear: When enabled, the RPC will send additional notification when
the situation that caused the alarm has been corrected. For example, when Notify
Upon Clear is enabled, the RPC will send initial notification when it detects that the
Emergency Shutoff function is initiated, and then send a second notification when
theunitdeterminesthatpowerhasbeenrestored.(Default=On)