8-16
Alarm Configuration
• Subject: This parameter is used to define the text that will appear in the "Subject"
field for all email notification messages generated by this alarm.
(Default="Alarm:PowerCycle")
• AlarmInputParameters: Provides access to a submenu that is used to Enable/
Disable the alarm at each Alarm Input, name Alarm Inputs, set trigger levels for
each Alarm Input and also select load shedding parameters for each Alarm Input.
Notes:
• TheAlarmInputAlarmmustbeenabledinordertoaccesstheAlarmInput
Parameters submenu.
• Text Interface:WhenaccessingtheAlarmInputParameterssubmenuvia
theTextInterface,firsttype11 and press [Enter] to access the first Alarm
InputParameterssubmenu.FromtheAlarmInputParameterssubmenu,key
inthenumberofthedesiredAlarmInputandthenpress[Enter] to display
theAlarmInputParameterssubmenuforanindividualAlarmInput.
• Web Browser Interface:ToaccesstheAlarmInputParameterssubmenu
viatheWebBrowserInterface,clicktheAlarmInputParametersbuttonatthe
bottomoftheAlarmInputconfigurationmenu.IntheWebBrowserInterface,
allAlarmInputParametersforallfourAlarmInputsmaybedefinedviaa
singlesubmenu.
The Alarm Input Parameters submenu will allow you to define the following
parameters for each Alarm Input:
Name: Can be used to define a unique name for each Alarm Input.
(Default=undefined.)
Enable:Enables/DisableseachAlarmInput.(Default=Off)
Level: Defines the trigger level for each Alarm Input as either Open or Closed.
For example, if the Level is set to "Open" and the Alarm Input Alarm is properly
configured, an alarm will be generated when the dry contact relay connected to
thecorrespondingAlarmInputisOpened.(Default=Open)
LoadShedding: Allow the Alarm Input Alarm to automatically shut off user
specified circuits or circuit groups when an Alarm is generated. This feature
works identically to the Load Shedding feature in the Over Temperature Alarms.
Formoreinformation,pleaserefertoSection8.1.1.(Default=undefined)