8-8
Alarm Configuration
8.3. The Lost Voltage (Line In) Alarm (RPC-40L8A4 Series Units Only)
The Lost Voltage (Line In) Alarm can provide notification after the power supply to the
RPC-40L8A4 unit has been interrupted.
Notes:
• TheLostVoltageAlarmisnotavailableonRPC-4850seriesunits.
• TheLostVoltage(LineIn)alarmwillprovidenotificationwhenoneofthe
availablepowersuppliesislostordisconnected.Thisalarmwillnotfunction
ifallinputpowertotheRPC-40L8A4unitislost.Toprovidenotificationwhen
allinputpowerislostandrestored,pleaseusethePowerCycleAlarmas
describedinSection8.6.
• InorderfortheRPC-40L8A4toprovidealarmnotificationviaEmail,
communication parameters must first be defined as described in
Section6.8.10.
• InorderfortheRPC-40L8A4toprovidealarmnotificationviaSyslog
Message,SyslogparametersmustfirstbedefinedandSyslogMessages
mustbeenabledasdescribedinSection6.8andSection11.
• InorderfortheRPC-40L8A4toprovidealarmnotificationviaSNMPTrap,
SNMPparametersmustfirstbedefined,andSNMPTrapsmustbeenabled
asdescribedinSection6.8.6andSection12.
To configure the Lost Voltage (Line In) Alarm, you must access the RPC-40L8A4
command mode using a password that permits Administrator Level commands. The
Lost Voltage Alarm Configuration menu offers the following parameters:
• TriggerEnable: Enables/Disables the trigger for this alarm. When Disabled, this
alarmwillbesuppressed.(Default=On)
Note:
• Tocancelanalarmwithoutcorrectingtheconditionthatcausedthealarm,
simplytoggletheTriggerEnableparameterOffandthenbackOnagain.
• TheTriggerEnable,NotifyonClear,EmailMessageandAddress1,2and
3Parametersallinclude"CopytoAllTriggers"optionsthatallowyouto
enable/disablethecorrespondingparameterforallRPC-40L8A4alarms.For
example,iftheLostVoltageAlarm'sTriggerEnableparameterissetto"On
(CopytoAllTriggers),thenallotherRPC-40L8A4alarmswillalsobeenabled.
• ResendDelay: Determines how long the RPC-40L8A4 will wait to resend an email
message generated by this alarm, when the initial attempt to send the notification
wasunsuccessful.(Default=60Minutes)
• NotifyUponClear: When enabled, the RPC-40L8A4 will send additional
notification when the situation that caused the alarm has been corrected. For
example, when Notify Upon Clear is enabled, the RPC-40L8A4 will send initial
notification when it detects that one of it's power supplies has been lost or
disconnected, and then send a second notification when it determines that power
hasbeenrestored.(Default=On)