8-6
Alarm Configuration
8.2. The Circuit Breaker Open Alarm (RPC-40L8A4 Series Units Only)
The Circuit Breaker Alarm is intended to provide notification in the event that one of the
RPC-40L8A4 series unit's fuse is blown. When a fuse is blown, the RPC-40L8A4 can
provide prompt notification via Email, Syslog Message or SNMP Trap.
Notes:
• TheCircuitBreakerOpenAlarmisnotavailableonRPC-4850seriesunits.
• InorderfortheRPC-40L8A4toprovidealarmnotificationviaEmail,
communication parameters must first be defined as described in
Section6.8.10.
• InorderfortheRPC-40L8A4toprovidealarmnotificationviaSyslog
Message,SyslogparametersmustfirstbedefinedandSyslogMessages
mustbeenabledasdescribedinSection6.8andSection11.
• InorderfortheRPC-40L8A4toprovidealarmnotificationviaSNMPTrap,
SNMPparametersmustfirstbedefined,andSNMPTrapsmustbeenabled
asdescribedinSection6.8.6andSection12.
To configure the Circuit Breaker Alarm, you must access the RPC-40L8A4 command
mode using a password that permits Administrator Level commands. The Circuit
Breaker Open Alarm Configuration Menu offers the following parameters:
• TriggerEnable: Enables/Disables the trigger for this alarm. When Disabled, this
alarmwillbesuppressed.(Default=On)
Note:
• Whenanalarmisgenerated,tocancelanalarmwithoutcorrectingthe
conditionthatcausedthealarm,simplytoggletheTriggerEnableparameter
OffandthenbackOnagain.
• TheTriggerEnable,NotifyonClear,EmailMessageandAddress1,2and
3Parametersallinclude"CopytoAllTriggers"optionsthatallowyouto
enable/disablethecorrespondingparameterforallRPC-40L8A4alarms.For
example,iftheCircuitBreakerOpenAlarm'sTriggerEnableparameterisset
to"On(CopytoAllTriggers),thenallotherRPC-40L8A4alarmswillalsobe
enabled.
• ResendDelay: Determines how long the RPC-40L8A4 will wait to resend an email
message generated by this alarm, when the initial attempt to send the notification
wasunsuccessful.(Default=60Minutes)
• NotifyUponClear: When this item is enabled, the unit will send additional
notification when the situation that caused the alarm has been corrected. For
example, when Notify Upon Clear is enabled, the unit can send initial notification
when it detects a blown fuse, and then send a second notification when it
determinesthatthefusehasbeenreplaced.(Default=On)
• EmailMessage:Enables/Disablesemailnotificationforthisalarm.(Default=On)